The text inside the bar will indicate the specific warning or alarm. If there is more than one alarm
present the text will scroll slowly through all current alarm conditions. Besides the errors listed
below, see also
Miscellaneous touchscreen controller errors on page

8.3.2 Maximum ignition trials error

Issue
Error – Ignition Failure after
3 tries boiler has failed to
ignite on 3 successive
attempts. Boiler is in lockout
for 1 hour, then repeats 3-try
sequence. Consult service
technician if error recurs.
Maximum Ignition Trials Error
Diagnosis
No spark when
Check that ignition lead is secure at the
igniting. Ignition
control module and at the probe.
probe/flame sensor
disconnected.
Manual gas shutoff is
Check for gas flow. Open manual gas
closed or gas line not
shutoff and reset boiler.
fully purged.
Gap between ignition
Adjust ignition probe rod gap between ⅛
probe rods is too large
and 3/16th (3.2-4.7 mm).
or too small.
Spark, but no ignition. Check spark module is sending power
to gas valve – close gas supply, then
disconnect (black) electric housing from
face of gas valve, gently spread plastic
tabs to open, and look for 24vac voltage
during an ignition cycle. Replace module
if no current detected
Boiler ignites, but
Ensure the pressure vessel is grounded.
shuts off at the end of
Check the ignition probe/flame sensor
the ignition trial.
is electrically isolated from the vessel,
Improperly grounded
and its ceramic insulator is intact.
pressure
Replace ignition lead Replace spark
vessel/burner or
module.
unserviceable ignition
lead or spark module.