7 | Installation
62/174
3. If a cooler of the pressure absorber system is mounted in the base, the two rear fixing clips
cannot be mounted. In this case, mount the fixing clips at fixing points located more to the
front. Mount the fixing clips with bolts M8.
Fig. 43: Fixing clips (front)
4. Bolt the base to the cross member using a bolt-and-washer assembly M8x25, a nut-and-
washer assembly M8 and 2 conical spring washers.
Fig. 45: Bolting the base to the cross member
5. Mount the tension brace on the base using 4 bolts M8.
Fig. 46: Mounting the tension brace
8DJH • Installation and Operating Instructions • Version 11 • 500-8384.9
Fig. 44: Possible positions for fixing clips
(rear)
Bolt-and-washer assembly M8x25
1
Conical spring washer (2x)
2
3
Nut-and-washer assembly M8
Tension brace
1