Siemens 8DJH Installation And Operating Instructions Manual page 107

Medium-voltage switchgear
Table of Contents

Advertisement

Tab. 44: Mounting position of cable-type current transformers 4MC7032 and 4MC7033
Instrument trans-
4MC7032
former type
Panel width
310 mm
Instrument trans-
80/150 mm
former height
Mounting position
Fig. 130: Principle of installation for 4MC7032 and 4MC7033
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
4MC7033
430 mm
65/110/170 mm
▪ To provide enough space for the instrument transformer wires, place the current
transformers slightly turned on the transformer mounting plate.
▪ Due to their height, mounted current transformers can reach into the cable basement.
430 mm
285 mm
INFORMATION
Cup head bolt M8x20
1
Extension of adjustment rail
2
(optional)
3
Adjustment rail
4
Self-tapping Torx bolt M6x16
5
Transformer mounting plate
6
Current transformer
7
Cable clamp
8
Cable bracket
9
Nut-and-washer assembly M8
Installation | 7
500 mm
285 mm
107/174