7.21.2 Connecting high-voltage cables

500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Common features and suitable cable plugs [▶ Page 16, "Cable connection"].
Cable connection type A
▪ Transformer feeder
L1
Fig. 124: Installation of cable T-plug
(example)
1. Remove the cable compartment cover [▶ Page 125, "Removing and mounting the cable
compartment cover"].
2. The cross member
7
mounting the cross member"].
3. Remove the upper part of the cable clamps
4. Pre-adjust the cable bracket
5. Optionally: Mount the cable-type current transformers ( [▶ Page 106, "Mounting the cable-
type current transformers"]).
6. Fit the cable plugs on the conductor ends according to the manufacturer's instructions.
7. Optionally: Mount the ring-core current sensors [▶ Page 110, "Installing ring-core current
sensors at the cable connection"].
8. Optionally: Mount the voltage sensors [▶ Page 112, "Installing voltage sensors"].
9. Carefully coat the push-on surfaces of the cable plugs and the bushings with the delivered
mounting paste (see scope of supply of the cable plugs).
L2
L3
Cable T-plug (phase L1)
1
Cable T-plug (phase L2)
2
Cable T-plug (phase L3)
3
Earthing cable for plug housing and cable
4
shield
Cable bracket
5
Cable clamp
6
Cross member (removable)
7
Bushing
8
can be removed to swing in the cables [▶ Page 126, "Removing and
.
6
and the lower part of the cable clamps.
5
Installation | 7
Cable connection type C
▪ Ring-main feeder
▪ Circuit-breaker feeder
L1
L2
L3
103/174