Siemens 8DJH Installation And Operating Instructions Manual page 93

Medium-voltage switchgear
Table of Contents

Advertisement

Tab. 42: Connection possibilities for the connecting cable
Type busbar-busbar
Upper current transformer connection
1
Lower current transformer connection
2
500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
Type busbar-cable
Type cable-busbar
1. Undo the hexagon head bolt and conical spring washer at the voltage transformer.
2. Mount the control cap together with the connecting cable onto the voltage transformer.
(Tightening torque: 20 Nm). At the metering panel type busbar-busbar mount only the
connecting cable without control cap.
Fig. 110: Mounting the control cap
Type cable-cable
Control cap
3
Connecting cable
4
1
2
3
4
5
6
7
8
9
Installation | 7
Voltage transformer
Control cap
Nut-and-washer assembly M8
Retaining clip for control cap
Plain washer
Fixing bracket
Threaded stud M8
Connecting cable
Cable lug
93/174