Recurring Activities; Removing And Mounting The Cable Compartment Cover - Siemens 8DJH Installation And Operating Instructions Manual

Medium-voltage switchgear
Table of Contents

Advertisement

7.22 Recurring activities

7.22.1 Removing and mounting the cable compartment cover

500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
1. Switch off auxiliary voltage.
2. Discharge the spring energy store.
3. Remove the front cover, [▶ Page 127, "Removing and mounting the front cover"] observe
the instructions specified there.
4. Connect the customer wiring
terminals (e.g. CAPDIS S2+, short-circuit indicators) according to the circuit diagrams, and
lay it such that the wires cannot come into contact with moving parts or heat sources.
5. If available, use the wiring duct
ducts 
.
2
6. Lead the secondary wires of the current transformers and voltage transformers through steel
mesh tubes or steel tubes in a shielded way into a lateral wiring duct.
7. Earth the steel mesh tubes or steel tubes with metal cable straps.
8. Avoid extra-long secondary wires or lay them in the wiring ducts 
duct 
in a meandering pattern.
5
Fig. 165: Secondary wires laid in a meandering pattern
9. Wire routing to the side is possible through the cut out cap 
10. For wire routing from below, use screened cable plugs.
11. Do not switch on auxiliary voltage yet.
Live parts
Touching live parts leads to a life-endangering electric shock. Observe the Five Safety Rules:
⇨ Isolate.
⇨ Secure against reclosing.
⇨ Verify safe isolation from supply.
⇨ Earth and short-circuit.
⇨ Cover or barrier adjacent live parts
To remove the cable compartment cover, the associated feeder must be earthed.
Unbolted cable compartment cover
In certain panels, the cable compartment cover is bolted on additionally. If the cable
compartment cover is not bolted on, the panels lose their resistance to internal faults. This
can cause death or serious injury due to an internal arc.
⇨ Always screw on the corresponding cable compartment covers additionally after
mounting the cable compartment cover.
to the terminal strip
7
6
on the operating mechanism box and the lateral wiring
1
DANGER
WARNING
Installation | 7
or directly to the equipment
and
or the fixing
1
2
.
3
125/174