500-8384.9 • Version 11 • Installation and Operating Instructions • 8DJH
3. Push the surge arrester plate
Use hexagon nuts M12 
Fig. 126: Mounting the surge arrester plate
4. Fasten the upper cross member with 4 self-tapping bolts M6
5. Fasten the surge arrester plate with 2 hexagon head bolts M8x16 % and plain washers
the upper cross member.
Fig. 127: Mounting the upper cross member Fig. 128: Fastening the surge arrester plate
6. Earth the cable shields with cable lugs and earthing bolts M10 at the upper cross member.
Fig. 129: Earthing the cable shields
7. Observe the minimum distances according to the manufacturer's instructions while
connecting non-screened cable plugs or surge arresters.
The use of RICS5xxx cable plugs with RDA in panels with a width of 310 mm is allowed
under normal ambient conditions according to IEC 62271-1 despite the reduced distance.
✓ The installation of the Raychem RICS5xxx cable plug with RDA is completed.
between the hexagon nuts of the adapter feet, and tighten.
3
with conical spring washers 
2
Installation | 7
.
4
.
1
Cable shield, phase L1
1
Cable shield, phase L2
2
Cable shield, phase L3
3
Upper cross member
4
to
6