Positions (Of Valve Ports): Define/Check - AUMA SAEx 07.2 Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2 / SAREx 07.2
ACExC 01.2 Non-Intrusive Modbus TCP/IP
Example
Information
10.1.5.

Positions (of valve ports): define/check

Information
Information
SAREx 16.2 Control unit: electronic (MWG)
Multiport valve M1140
MPV home port M1162
Set?
Successful homeport setting is visualised by a black circle on the actuator controls
display: .
Reset homeport (zero point)
Required user level: Specialist (4) or higher.
Customer settings M0041
Multiport valve M1140
Reset MPV homeport M2863
Reset?
Successful resetting of the homeport is shown by a white circle with a black line on
the actuator controls display: .
Configuration of digital input
Required user level: Specialist (4).
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Use input DIN 5 for "Set home port" signal:
Parameters: Signal DIN 5 M0122
Setting value: MPV set home pos. (wiring diagram designation:
The logic for the digital inputs may be inverted. Depending on the parameter setting
(e.g. Coding DIN 5M0127), the input is either High active or Low active. Default setting
is High active.
Each position can be set to any value between 0° and 360° (one full turn of the valve).
Prior to setting the positions, the home port must be defined (parameter MPV home
port).
This corresponds to the zero position of the valve (0° or 360° of one full valve turn
as well as 0 % or 100 % of position feedback).
The positions of the valve ports have to be set afterwards.
Customer settings M0041
Multiport valve M1140
MPV positions M1149
Setting ranges: 0.0 to 359.9°
Default values: 0.0° (for all positions)
If desired, positions can be preset in the factory.
The first position must always be located at 0.0°.
Example configuration for a multiport valve comprising 8 ports: All 8 positions are
evenly spread across 360°.
Position 1 = 0.0 (bzw. 359,9°)
Position 2 = 45.0
Position 3 = 90.0
Position 4 = 135.0
Position 5 = 180.0
Position 6 = 225.0
Commissioning (basic settings)
Home port
)
53