Operate To Position Via Push Buttons Of The Local Controls - AUMA SAEx 07.2 Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Commissioning (basic settings)
10.1.6.

Operate to position via push buttons of the local controls

54
SAEx 07.2
SAEx 16.2 / SAREx 07.2
Position 7 = 270.0
Position 8 = 315.0
The positions must be set in subsequent sequence (descending/ascending).
To operate to a position via push buttons of the local controls, status indication S0017
must be shown (refer to <Indications in the display>).
Figure 65: Status indication of multiport valve (selector switch in position OFF)
Operation in clockwise or counterclockwise direction:
When changing the selector switch to position Local control (LOCAL), the display
changes:
Figure 66: Status indication of multiport valve (selector switch in position LOCAL)
As a consequence, the valve can be operated into clockwise or counterclockwise
direction (display shows CW or CCW)
Direct operation to a position:
When selector switch is in position 0 (OFF), the function "Direct operation to a position
via push buttons" is activated via ->STEP (push button
Figure 67: Status indication of multiport valve (selector switch in position OFF)
When changing the selector switch to position Local control (LOCAL), the display
changes for selection of the desired position:
Figure 68: Status indication of multiport valve (selector switch in position LOCAL)
Select the desired position (P1, P2, ...) via push buttons
via Ok (push button
).
→ The operation is issued as soon as push button Ok is pressed.
SAREx 16.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Modbus TCP/IP
) (display shows ->JOG).
and confirm selection