Type Of Seating: Check/Edit For End Positions - AUMA SG 05.1 Operation Instructions Manual

Control unit: electronic (mwg) with actuator controls aumatic ac 01.1 non-intrusive
Table of Contents

Advertisement

Commissioning (basic settings)
9.4

Type of seating: check/edit for end positions

Limit seating
Torque seating
40
SG 05.1
SG 12.1/SGR 05.1
Valve damage due to incorrect setting!
The torque must suit the valve.
Only change the setting with the consent of the valve manufacturer.
The limit switching is set in such a way that the actuator switches off at the desired
switching points. The torque switching acts as overload protection for the valve.
The torque switching is set to the desired tripping torque. After reaching the tripping
torque the actuator is turned off.
The limit seating is used to signal that the limit switching will trip shortly before
reaching the set tripping torque. If this is not the case, one of the following fault
signals is displayed:
TSO FAULTS
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SEATING MODE (M11)
VIEW (M110)
EDIT (M111)
OPEN POSITION (M11_0)
CLOSED POSITION (M11_1)
Default value:
LIMIT
Step by step:
1.
Set selector switch to position 0 (OFF).
2.
Press
C
and hold it down for approx. 3 seconds.
Display indicates:
MAIN MENU
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3.
Press .
Display indicates:
MAIN MENU
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4.
Press
.
Display indicates:
SETTINGS
SET LIMIT SWITCHES
SEATING MODE
TORQUE
SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU
or
(menu S1).
TSC FAULTS
M0
M1
M10