Accessories for electrical connection

6.4.1.

Actuator controls on wall bracket

Design
Application
SAREx 16.2 Control unit: electronic (MWG)
Figure 31: Earth connection for wall bracket
External earth connection (U-bracket) for connection to equipotential compensation.
Table 20:
Terminal cross sections and earth connection tightening torques
Conductor type
Solid wire and stranded
Fine stranded
For fine stranded (flexible) wires, connection is made via cable lugs/ring terminals. When connecting
two individual wires with a U-bracket, cross sections have to be identical.
Figure 32: Design principle with wall bracket (example)
[1]
Wall bracket
[2]
Connecting cables
[3]
Electrical connection of wall bracket (XM)
[4]
Electrical connection of actuator (XA)
[5]
Electrical connection of actuator controls (XK) - customer plug
The wall bracket allows separate mounting of actuator controls and actuator.
If the actuator cannot be accessed safely.
Terminal cross sections
2.5 mm² to 6 mm²
1.5 mm² to 4 mm²
Electrical connection
Tightening torques
3
4 Nm
3
4 Nm