Gear Reduction Ratio: Set/Check; Number Of Ports (Positions); Home Port (Zero Position): Set - AUMA SAEx 07.2 Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

Commissioning (basic settings)
10.1.2.

Gear reduction ratio: set/check

10.1.3.

Number of ports (positions)

10.1.4.

Home port (zero position): set

Information
Set home port
52
SAEx 07.2
SAEx 16.2 / SAREx 07.2
The reduction ratio of the gear stage of the actuator mounted to the valve gearbox
must be set here. To facilitate adjustment, a selection table of supported gearboxes
is available.
Required user level: Specialist (4) or higher.
Customer settings M0041
Multiport valve M1140
Reduction ratio M1143
Default values: GS50.3
Setting values:
Table 25: Selection of gearboxes supported by AUMA
Sizes GS 50.3
GS 125.3
GS50.3
GS63.3
GS80.3
GS100.3
GS100.3/VZ2.3
GS100.3/VZ3.3
GS100.3/VZ4.3
GS125.3
GS125.3/VZ2.3
GS125.3/VZ3.3
GS125.3/VZ4.3
Number of valve ports (positions)
Required user level: Specialist (4) or higher.
Customer settings M0041
Multiport valve M1140
Number of ports M1141
Default value: 8
Setting ranges:
In operation mode Remote 2 to 10
In operation mode Local or Fieldbus 2 to 16
The home port is the zero position (0° or 360° of one turn) and is consequently the
starting point for all other intermediate positions.
Set the gear reduction ratio (parameter Reduction ratio M1143) and the actuator
type (parameter Actuator type M1142) prior to setting the home port.
1.
Position multiport valve to zero position either via manual operation (handweel)
or via motor operation (via push buttons of local controls)
2.
In a next step, confirm this position (with Yes) as homeport via parameter MPV
home port M1162.
As an alternative, the home port position can also be confirmed via a signal at
a digital input. To this end, a digital input has to be available and configured.
Set home port (zero position) via parameter
Required user level: Specialist (4) or higher.
Customer settings M0041
SAREx 16.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Modbus TCP/IP
Sizes GS160.3
GS 250.3
GS160.3
GS160.3/GZ160.3(4:1)
GS160.3/GZ160.3(8:1)
GS200.3
GS200.3/GZ200.3(4:1)
GS200.3/GZ200.3(8:1)
GS250.3
GS250.3/GZ250.3(4:1)
GS250.3/GZ250.3(8:1)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Saex 16.2Sarex 07.2Sarex 16.2

Table of Contents