Setting of CHK_GOOSERCV (Function ID: 223501)
Setting item
CHK_GOOSERCV:Sw
--- / Serious error / Serious error(Comm) /
CHK_GOOSERCV:Lvl
Setting of CHK_PING (Function ID: 223601 and 223602)
Setting item
CHK_PING1:Sw
--- / Serious error / Serious error(Comm) /
CHK_PING1:Lvl
PING_IP_ADRS
PING_IP_ADRS2
PING_IP_ADRS3
PING_IP_ADRS4
CHK_PING2:Sw
--- / Serious error / Serious error(Comm) /
CHK_PING2:Lvl
PING_IP_ADRS
PING_IP_ADRS2
PING_IP_ADRS3
PING_IP_ADRS4
Setting of CHK_CMLV (Function ID: 224001)
Setting item
CHK_CMLV_DAT:Sw
--- / Serious error / Serious error(Comm) /
CHK_CMLV_DAT:Lvl
Setting of PRP_LRE (Function ID: 224101)
Setting item
CHK_LRE:Sw
--- / Serious error / Serious error(Comm) /
CHK_LRE:Lvl
Setting of CHK_DPOSSYN (Function ID: 229001)
Setting item
CHK_DPOSSYN1:Sw
--- / Serious error / Serious error(Comm) /
CHK_DPOSSYN1:ULvl
Range
Off / On
Minor error / Alarm / Warning
Range
Off / On
Minor error / Alarm / Warning
0 - 255
0 - 255
0 - 255
0 - 255
Off / On
Minor error / Alarm / Warning
0 - 255
0 - 255
0 - 255
0 - 255
Range
Off / On
Minor error / Alarm/ Warning
Range
Off / On
Minor error / Alarm/ Warning
Range
Off / On
Minor error / Alarm / Warning
- 1118 -
Contents
Enable switch
Error level
Contents
Enable switch
Error level
Ping target IP address
Enable switch
Error level
Ping target IP address
Contents
Enable switch
Error level
Contents
Enable switch
Error level
Contents
Enable switch to supervising the DPSY01
Error level for undefined error at DPSY01
6F2S1915 (0.46)
Default setting value
Notes
On
Minor error
Default setting value
Notes
Off
Minor error
192
168
1
1
Off
Minor error
192
168
1
1
Default setting value
Notes
On
Minor error
Default setting value
Notes
On
Serious error (Comm)
Default setting
Notes
value
On
Alarm
GRZ200 (Soft 031 & 032)