Download Print this page

Toshiba GR200 Series Instruction Manual page 1093

Hide thumbs Also See for GR200 Series:

Advertisement

Generic supervision tasks
Displaying errors regarding to common problems are summarized in Table 10.2-1; the error is
cleared when recovered
Table 10.2-1 Supervision items and error levels for generic
Sec. No. Supervision items (Screen message)
10.2.1 Mismatch between ROM and RAM data (ROM/RAM error)
10.2.2 Supervision of check-sum error (SUM error)
10.2.3 Supervision of RAM (RAM error)
10.2.4 Supervision of ECC on memory (ECC error)
10.2.5 Supervision of MRAM (MRAM)
10.2.6 Supervision of FPGA (FPGA error)
10.2.7 Supervision of program codes (CPU error)
10.2.8 Supervision of task operation (RUN error)
10.2.9 Detecting non-maskable interrupt (NMI error)
10.2.10 Supervision of sampling period (SMP error)
10.2.11 Supervision of setting data (Setting error)
10.2.12 Supervision of real-time clock (RTC error)
10.2.13 Supervision of A/D accuracy on VCT#1 (AI#1 ACC error)
10.2.14 Abnormal current flowing in CT (CT error)
10.2.15 Current transformer failure (CT fail)
10.2.16 Supervision of current in zero-sequence (I0 error)
10.2.17 Supervision of voltage in negative-sequence (V2 error)
10.2.18 Supervision of voltage in zero-sequence (VZ error)
10.2.19 Supervision of binary IO module#1 (BIO#1 error)
10.2.20 Supervision of binary IO module#2 (BIO#2 error)
10.2.21 Supervision of binary IO module#3 (BIO#3 error)
10.2.22 Supervision of binary IO module#4 (BIO#4 error)
10.2.23 Supervision of binary IO module#5 (BIO#5 error)
10.2.24 Supervision of binary IO module#6 (BIO#6 error)
10.2.25 Supervision of binary IO module#7 (BIO#7 error)
10.2.26 Supervision of binary IO module#8 (BIO#8 error)
10.2.27 Supervision of human machine interface (HMI error)
10.2.28 Supervision of power supply module (Power error)
10.2.29 Supervision of data in PLC function (PLC data error)
10.2.30 Voltage transformer failure (VT fail)
10.2.31 Supervision of circuit breaker contacts (CB1/CB2 fail)
- 1072 -
6F2S1915 (0.46)
Detailed
Error
Info.
Lvl.
LED
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
3
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
3
ON
Displayed
1
ON
Displayed
3
ON
N/A
3
ON
N/A
3
ON
N/A
3
ON
N/A
3
ON
N/A
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
1
ON
Displayed
3
ON
Displayed
3
ON
N/A
3
ON
Displayed
3
ON
N/A
3
ON
N/A
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200