10.2.20 Supervision of binary IO module#2 (BIO#2 error)
A supervision function is provided to detect the operation failure in the second binary IO
modules (BIO)†.
†Note: The function can operate for respective BIO modules mounted in the IED; the user
should have settings in them, which are located at the IO slot identified with the
number.
Error level
(i)
Generally, the default error level has been set at level 1 (Serious error
can program the level using setting [CHK_BIO2:LVl] when the BIO module at the IO#2
should be supervised; then, set On for the setting [CHK_BIO2:Sw]. The manufacturer sets one
(1) second to detect the failure; it is reset within a second when the failure is cleared.
Note: When the error is detected, the entire operation of the IED is stopped forcibly.
1
Note: The location of the IO slot is discussed in Chapter
2
and module slot
Error message
(ii)
When detecting an error, an error message can be shown on the LCD screen and an LED is lit.
Table 10.2-41 Error messages provided by the supervisor in CHK_BIO2
Message and level
BIO#2 error
Error level
Table 10.2-42 Detailed information in Hexadecimal in CHK_BIO2
Display
area
00000001: CRC error
Top
00000002: Connection error
row
00000004: Read back error
Middle
Count number by the connection error
row
Bottom
(No message displayed)
row
.
Meaning of the information
Detection of the BIO failure at IO slot#2
Serious error (Level 1)
Meaning of the detailed information
Left column
- 1093 -
). For example, the user
1
Technical description: IED case
Right column
Count number by the CRC error
Count number by the read-back error
(No message displayed)
6F2S1915 (0.46)
slot
2
GRZ200 (Soft 031 & 032)