Setting event list
(iii)
The user can set information with regard to the event of an IED using the event list function.
Interlock configurator
(iv)
The user can program conditions for executing to control the primary equipment using the
interlock (ILK) configurator. For example, controlling a circuit breaker (open and closing) is
significant; note not induce mal-operations caused by improper conditions; otherwise a severe
fault/blackout results in. The ILK configurator can provide the user to program conditions
concerning the status of the power system. For more information of the ILK, see chapter
Control and monitoring application
IEC 61850 configuration tool
The user can configure conversion data for the IEC61850 communication†, provided the IED
exchanges the data with the SAS. The user also configures a logical device, a logical node,
Goose publish information, and Goose subscribe information. For setting and configuration for
the
IEC61850
communication
communication
".
†Note: The configuration is possible when the IED software has the IEC61850 protocol.
To confirmed the implementation of IEC61850 protocol, the user needs to check
the IED ordering code (for more information, see
IEC 60870-5-103 configuration tool
The user can edit the data of the IEC 60870-5-103 protocol† to perform communications
between IEDs. The IEC 60870-5-103 data consists of the IEC 60870-5-103 Slave and the
IEC60870-5-103 Master data; the user can edit either the Slave Data or the Master Data‡ at
a time.
†Note: The configuration is possible when the IED software has the IEC 60870-5-103. To
confirmed the implementation of IEC61850 protocol, the user needs to check the
IED ordering code (for more information, see
shown when the IED software does not have the IEC 60870-5-103.
‡Note: Editing the master data is not available at present.
MIMIC configuration tool
When the IED has a large LCD, the user can create user-preferred screens using the MIMIC
configurator. The large LCD will be able to display measurement values, diagrams and others
after the configuration. Note that the MIMIC is not available when the standard LCD is
equipped for the IED.
.
Communication
see
Chapter
Appendix: Ordering
- 992 -
6F2S1915 (0.46)
protocol: IEC 61850
Appendix: Ordering
).
). The tool is not
GRZ200 (Soft 031 & 032)