Page 3
The instructions contained in this manual are not intended to cover all of the details or variations in equipment, or to provide for every possible contingency concerning installation, operation, or maintenance. Should further information be required or if problems arise which are not covered sufficiently, contact your Toshiba sales office or call Toshiba Power Electronics Division at 855-803-7087 Nothing in this manual shall alter Toshiba International Corporation’s standard terms and conditions or the...
Page 4
SCiB ENERGY STORAGE SYSTEM Please complete the following information and retain for your records. JOB NUMBER MODEL NUMBER SERIAL NUMBER APPLICATION SHIPMENT DATE INSTALLATION DATE STARTUP PERFORMED BY G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 5
(See https://www.toshiba.com/tic/industrial/uninterruptible-power-systems. ) Toshiba and SCiB are registered trademarks of the Toshiba Corporation. All other product or trade references appearing in this manual are registered trademarks of their respective owners. Toshiba International Corporation shall not be liable for direct, indirect, special, or consequential damages resulting from the use of the information contained within this manual.
Introduction This manual provides information on how to safely install and operate your G9000 Series UPS System with the SCiB Energy Storage System (ESS). This manual includes a section of general safety instructions that describes the warning labels and symbols that are used throughout the manual. Read the manual completely before installing, operating, or performing maintenance on this equipment.
Ground Symbol indicates the location of the equipment grounding conductor. Electrical – Voltage & Shock Hazard Symbol indicates parts inside may cause electric shock. Explosion Hazard Symbol indicates parts may explode. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety practices. • Be trained in rendering first aid. For further information on workplace safety visit www.osha.gov. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Factory Authorized Personnel Factory authorized personnel have been factory trained and certified to install, service, and repair the G9000 UPS & SCiB Energy Storage System (ESS). Contact the Toshiba Customer Support Center for assistance in locating the factory- authorized personnel nearest you.
Hazardous DC voltages are present in the system. This hazard will always be present in a battery system including when it is offline. The Toshiba SCiB Modules within the SCiB ESS can present a risk of electrical shock and high short circuit current. Use extreme caution when installing and maintaining the system.
Disclaimer IN NO EVENT WILL TOSHIBA CORPORATION BE RESPONSIBLE OR LIABLE FOR EITHER INDIRECT OR CONSEQUENTIAL DAMAGE OR INJURY THAT MAY COME FROM THE MISUSE OF THIS EQUIPMENT. ANY MODIFICATIONS WITHOUT AUTHORIZATION BY TOSHIBA COULD RESULT IN PERSONAL INJURIES, DEATH OR DESTRUCTION OF THE SCIB ESS.
Contact the authorized Toshiba Customer Support Center or an authorized Toshiba representative for information on proper disposal of SCiB ESS components. It is illegal to dispose of certain components without conforming to environmental regulations for industrial/commercial waste. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Always use a crane, forklift, or pallet jack for transporting and positioning the units. Pushing/pulling on the sides of the unit to move it may result in damage to the SCiB ESS. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
(e.g. insulating tape) (Ref. Section 13, MSDS SB-SDS-P0045E dated 7/21/2011) For any questions regarding disposal please contact Toshiba Customer Support Center (855) 803-7087. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
• If provided, DO NOT remove the protective plastic sheet cover until installation. • Immediately report any abnormalities to Toshiba Customer Support Center or an authorized representative. Unpacking the SCiB Energy Storage Cabinet CAUTION TOP HEAVY EQUIPMENT. THIS EQUIPMENT WILL TIP OVER EASILY UNTIL FIXED IN PLACE.
Page 19
Front SCIB ENERGY STORAGE SHIPPING FIGURE 4.1: CRATE G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
DO NOT tilt units when lifting and/or transporting. Minimize the impact when lowering the cabinet to the floor. Insert the forks here FIGURE 4.2: SCIB ENERGY STORAGE CABINET: FRONT VIEW - FORK ACCESS DIMENSIONS IN CHANNEL BASE G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Below are representative warning labels and their location on the SCiB Energy Storage System. NOTICE Make sure all the warning labels are installed in the appropriate locations. If a label is missing or illegible, contact Toshiba Customer Support Center or an authorized representative. NOTICE The SCiB Energy Storage Cabinet contains Lithium Ion Batteries.
The optimal relative humidity at the storage location should be between 50 – 60%. • Humidity must not exceed 90%. • Avoid locations where UPS may be exposed to corrosive gas. • Avoid locations with dirt and/or dust. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
2. DO NOT insert metal objects or combustible materials in the ventilation slots of the SCiB ESS. 3. DO NOT place, hang, or paste any objects on the exterior surfaces of the SCiB ESS. 4. DO NOT attempt to disassemble, modify, or repair the SCiB ESS. Call your Toshiba sales representative for repair information.
Misuse of equipment could result in injury and equipment damage. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the misuse of this equipment. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
SCiB ESS after initial installation. Electrical shock, injury or UPS/ESS failure may occur if non-authorized technicians attempt to modify or relocate the SCiB ESS. Please contact Toshiba Customer Support Center if you plan to move or make modifications to the UPS CAUTION Install the UPS system in a controlled environment.
Voltage exists at battery terminals. Proper PPE should be worn when making electrical connections G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 27
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 28
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 29
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 30
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 31
G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Once unpacked and moved to final location, install the ESS using the four holes in the channel base. Anchor the unit us- ing appropriate hardware. Reference Figure 7.6 for base dimensions and anchoring hole details.. FIGURE 7.6: BOTTOM VIEW OF SCIB ESS G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
7.7. Note: Use only S-STP Ethernet Cable. Use of non S-STP Ethernet cable will cause loss of communication between cabinets. This step applies to ESS with multiple cabinets only. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
FIGURE 7.11: 2-PORT HALF DUPLEX CONNECTION CH B+ (Z) CH A+ (B) CH A- (A) CH B- (Y) P5 (RS 485) GND/Shield FIGURE 7.12: 4-PORT FULL DUPLEX CONNECTION G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 39
If firmware version 2.01 is installed on the SCiB ESS, a multi-drop/daisy-chain connection can be made to CN3 following the below diagram. This requires that the dip switches on the Toshiba Host board are set to half-duplex. This action should be performed by a technician.
7. The green LED will start flashing indicating the UPS is charging the batteries. 8. Once the batteries are fully charged, then the green LED will stay on. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
7. The green LED will start flashing indicating the UPS is charging the batteries. 8. Once the batteries are fully charged, then the green LED will stay on. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
480VAC, 5A, 2PH, 2W Maximum Number of ESS cabinets that may be paralleled by direct bus bar connection Maximum Number of ESS cabinets in a single UPS System G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
This software resides in TIC control board and acts as gateway to control one or up to eight G9000 SCiB Energy Storage Systems. Each cabinet contains two strings of 18 Toshiba SCiB Modules. The software should be setup where one sys- tem is a leader and the other systems are followers that will report to the leader system.
Blink Four battery module reaches Battery has reached the Temperature Warning Times Every Unit the warning-level set- heat level. Reduce heat to prevent fault. 5 Seconds point (default 55 G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
6. If optional fuse indicators are opened. (Only if installed) 7. If either of the micro-switches for the fuse trays is activated. 8. If battery breaker is opened. *value is subject to change. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Max. cell voltage (fault protected by BMU) 40019 Max. cell voltage indicated by 1mV/LSB (3.0V) Min. cell voltage (fault protected by BMU) 40020 Min. cell voltage indicated by 1mV/LSB (1.3V) G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 49
Right string min. cell temp. / 40040 cells indicated by 1°C/LSB. Usage cell temperature value in Right string. module No. range -40°C to 125°C Usage range: module No. 1 to 28. G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
1 – System has no fault. One or more contactors is open. ◦ Service (b5): 1 – System has not fault. Both contactors are closed. • Bits 6-7: contactor status ◦ 0 – Open; 1 – Closed G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 51
Bit 0: Left string contactor open ◦ Bit 1: Left string over cell temperature warning ◦ Bit 2: Left string over cell voltage warning ◦ Bit 3: Left string under cell voltage warning G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 52
During the 5 sec display, the cabinet ID (1 digit) will be on always; the warning or fault status (5 digits) will display from the highest digit to the lowest digit (0.5 sec on/off time for each digit) G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
CAB ID = 000 Bit 2 Abnormal Bit 3 Bit 4 Ready <560V Bit 5 Service No Fault Bit 6 Left String Close Bit 7 Right String Close G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 56
Bit 0 Breaker Status Breaker Open Fuse Status Fuse Normal Bit 1 Tray Status Tray Open Bit 2 Bit 3 Host-Host CAN COM Status Host-Host CAN COM Normal G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 57
Status Description Bit 0 Bit 1 Bit 2 Bit 3 Left String BMU to Host COMM Status Left String BMU to Host COMM Fault Bit 4 Bit 5 G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 58
Right String Contactor Open Bit 9 Right String Over Cell Temp Warning Bit 10 Right String Over Cell Voltage Warning Bit 11 Right String Under Cell Voltage Warning Bit 12 G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 59
Right String Contactor Open Bit 9 Right String Over Cell Temp Warning Bit 10 Right String Over Cell Voltage Warning Bit 11 Right String Under Cell Voltage Warning Bit 12 G9000 Series SCiB Energy Storage Cabinet Installation and Operation Manual – 98485-002...
Page 61