Download Print this page

Toshiba GR200 Series Instruction Manual page 1040

Hide thumbs Also See for GR200 Series:

Advertisement

of group settings (e.g., the 'SYS_CHG' signal; which has been connected with the trigger#9
using the setting [Trigger ID9], as default; we have been discussed in Chapter
description: Group setting for protection functions
Screen information
8.2.3
Figure 8.2-5 illustrates the structure about the 'Event Recored1' group, which can be shown
the latest event#1 at the top structure (line ○
occurred for the event#1. Preceding event#2, event#3, etc. are shown below the event#1.
Similarly, the information about the 'Event Record2' and 'Event Record3' groups are displayed
on the IED screen.
†Note: For more information about the screen operation, see Chapter
Record sub-menu
Screen scroll down
Figure 8.2-5 Event information grouped in the Event record1
Setup for the event recorder
8.2.4
Consider that a trip-command, which is denoted with Data ID '4A1001 8300001B6F', should
be sorted into the 'Event record1' group. The settings [End of E.Record-1]=256 and [End of
E.Record-2]=512 have been made as default; hence, we may select it with the trigger#157 by
setting the [Trigger ID157]= '4A1001 8300001B6F'. Set On-OFF for the [Trigger Mode157],
because the pulse-train of the trip command should be recorded along the pick-up and drop-off
times. Remember that the preferred name for the Trigger ID157 should be set using the [Event
Name157].
.
Event Record1
10:48
1/4
#1
2012-07-26
12:34:51.223
F.Record clear
On
#2
2012-07-25
10:56:12.021
Set group change
4
#3
2012-07-25
10:31:12.159
F.Record clear
On
#4
2012-07-23
23:56:12.159
- 1019 -
.)
). The lines ○
and ○
b
c
a
Event record1 list
b
The latest event#1
c Trigger inform ation
d
Trigger m ode inform ation
e
Event#2
f
Event#3
g
Event#4
6F2S1915 (0.46)
Technical
describes how an event
d
User interface:
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200