Error outputs with contacts and binary output circuits
(iii)
Automatic supervision function drives a contact of the power supply module (PWS)† when an
error occurs without warning; additionally, binary output circuits (BOs‡) will be locked out to
drive when serious error (Level 1=Critical error) is detected.
Table 10.1-4 FAIL contact, BO, LED outputs depending on levels
Error
Levels
0: No error
1:Serious
2:Serious(Comm.)
3:Minor
4:Alarm
5:Warning
Error output by PWS contact†
If serious error (Level1) is detected by Automatic supervision function, normally-closed-contact
(N/C) on FAIL1 and FAIL2 terminals is closed. On the other hand, the N/O contact is open on
the serious error, as shown in Table 10.1-4.
Locking out of BO circuit operation‡
BO is locked out to operate, when serious error (Level1) occurs. Serious error stops trip signal
generations to the BO circuit. When serious error is removed, the operation will be recovered.
†Note: See Chapter
is in Form-C; terminal-screw No. 2 & 4 (8 &10) are provided with the common.
‡Note: BO is discussed in Chapter
Affection of application operation by error levels
(iv)
The error levels influence the operation of relay and control and monitoring application.
Table 10.1-5 Operation states in the IED applications affected by the error levels
Levels
0: No error
1: Serious
2: Serious (Comm.)
3: Minor
4: Alarm
5: Warning
†Note: Serious (Comm.) can be related to communication of tele-protection applications.
PWS† contact outputs
FAIL1 terminal
Screw No. 1
Screw No. 3
(N/C)
(N/O)
Open
Closed
Closed
Open
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Technical description: Power supply module
Relay applications
Stopped
Not affected†
Not affected
Not affected
Not affected
FAIL2 terminal
Screw No. 7
Screw No. 9
(N/C)
(N/O)
Open
Closed
Closed
Open
Open
Closed
Open
Closed
Open
Closed
Open
Closed
Technical description: Binary output circuit
Control and monitoring applications
Not affected
Not affected
Not affected
- 1071 -
6F2S1915 (0.46)
BO‡ locked out
Not locked out
Locked out
Not locked out
Not locked out
Not locked out
Not locked out
. FAIL1 (FAIL2) contact
.
Stopped
Stopped
GRZ200 (Soft 031 & 032)
Error
LED
Off
On
On
On
Off
Off
Notes