Common tools
Project management
(i)
Project files are required to engage sub-engineering tools. The user can manage to read/write
the project file of the IED using the project management function. The user can also see the
contents of the project files.
Comparison
(ii)
When the user wishes to get the comparison between respective IEDs, using the compare
function the user can get the comparison data about Settings, Disturbance record binary
signals, PLCs, Interlock, Large LCD (MIMIC)†, IEC61850, and IEC60870-5-103 data†.
Pocket label creator
(iii)
The user can create the name label of LEDs and Function keys for the IED front panel using
a pocket label sheet, which is provided together with the IED. For more information with
regard the LEDs and Function keys, see Chapter
interface
.
Logging
(iv)
The user can view the recorded data with regard to the logging date/time. As the user can also
find operation recorded when an operator/engineer logs into the IED, analyzing a problem is
possible when an error is detected during the IED operations.
Double command block
(v)
For controlling, there is a principle that a first receiving-command shall be carried out
primarily. In other words, succeeding receiving-commands cannot have the right to run until
the first receiving-command is not completed to operate (that is, the principle of double
command blocking (DCB) is established). The principle is significant for the device protections;
hence, the user should DCB setting. For more information with regard to set the DCB, see
General control function: Common controls
Chapter
Monitoring tools
The user can monitor status and measurement value obtained in the IED using the monitoring
tools. All signals monitored are tabulated in the monitoring list dialog. When the user wishes
to monitor a signal, select a signal in the monitoring list dialog after the operation of the drag-
drop on the monitoring window. The monitoring tools can generate an exporting layout file in
the CSV; it also can obtain the layout file in the CSV.
Technical description: Human machine
.
- 990 -
6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)