10.2.37 Supervision of GOOSE publishing (LAN(GOOSE)error)
Publishing error in the IEC 61850 communication† is detected when a GOOSE message is not
received.
†Note: For more information about GOOSE, see Chapter
61850 communication
Error level
(i)
Generally, the default error level has been set at level 3 (Minor error), but the user can program
the
level
using
[CHK_GOOSERCV:Sw]. Detecting the error is expressed in five-minutes when the IED detects
no reception of the GOOSE. When the GOOSE is started to receive, it is reset in one-minute.
Error message
(ii)
When detecting errors, an error message can be shown on the LCD screen and an LED is lit.
Table 10.2-76 Error messages provided by the supervisor in CHK_GOOSERCV
Message and level
LAN(GOOSE) error
Error level
Table 10.2-77 Detailed information in Hexadecimal in CHK_GOOSERCV
Display
area
Top
Receipt state regarding to the GOOSE
row
subscribe information#1†
Middle
Receipt state regarding to the GOOSE
row
subscribe information#3†
Bottom
Receipt state regarding to the GOOSE
row
subscribe information#5†
†Note: "c000" is shown when no reception.
.
setting
[CHK_GOOSERCV:LVl];
Meaning of the information
Detection of the failure in GOOSE
Minor error (Level 3)
Meaning of the detailed information
Left column
- 1112 -
Communication protocol: IEC
then,
set
On
Right column
Receipt state regarding to the GOOSE
subscribe information#2†
Receipt state regarding to the GOOSE
subscribe information#4†
Receipt state regarding to the GOOSE
subscribe information#6†
6F2S1915 (0.46)
for
the
setting
GRZ200 (Soft 031 & 032)