Instruction/Handover
The installer has informed the operator about the maintenance work carried out.
The installer has informed the operator about possible modifications and repair work.
The installer has handed over the necessary documents to the operator.
Information on the intended operation of potable water installations:
- Stagnation must be avoided, regular potable water exchange must be ensured
- TPWH >= 60 °C must be maintained at the hot water outlet
- The circulation system must be designed in such a way that the potable water temperature does not fall below the station
outlet temperature of >= 60 °C by more than 5 K
- TPWC must be maintained at < 25 °C at the cold water outlet
Installer / Installation company
_____________________________________________________________
Date / Signature / Stamp
User
Maintenance report received
_____________________________________________________________
Date / Signature
¨
¨
¨