Technical description
3.4

Application example

Design temperatures: 60 °C hot water; 75 °C flow temperature storage cylinder circuit
(design according to DIN 1988-300)
Number
Residential
of X-45
building
stations
1 washbasin
1 kitchen sink
1 shower
1
7
2
48
3.5

Technical data

General information
Max. operating pressure
p s )
(
Max. operating tempera-
t s )
ture (
Ambient temperature
Empty weight
Connections
Storage cylinder circuit, po-
table water circuit, circula-
tion
Fill and drain ball valves
Storage cylinder circuit
Fluid
k v value
High-efficiency pump
138114082-V04.04.2022
Hospital room
Hotel
room
1 washbasin
1 washbasin
1 shower
1 shower
7
7
28
26
10 bar
95 °C
2 - 35 °C
Approx. 15 kg
G 1 flat sealing external
thread
G 3/4 external thread, for
hose screw connection
Heating water according
to VDI 2035/Ö-Norm
(Austrian standard)
H5195-1, fluid category ≤
3 according to DIN EN
1717, (see Oventrop in-
formation sheet on corro-
sion protection in the
appendix)
3.41 m3/h
Wilo PARA 15-130/8-75/
LIN-9
Power consumption in
operation 2 - 75 W
Series shower
Buffer storage
installation
cylinder volume [l]
Number of showers at
6 l/min 60 °C PWH
(simultaneity factor
80%)
9
800
18
1500
Potable water circuit
Fluid
Discharge capacity
(at Δ T = 15K)
k v value
Safety valve
- Control range:
- Controller presetting:
Required
boiler output
[kW]
39
82
Potable water (see Oven-
trop information sheet on
corrosion protection in
the appendix)
Notice
Damage to the
measuring turbine due
to chemical
influences!
Water treatment
additives in high
concentrations can
damage the measuring
turbine.
!
Ensure that the
permissible limits
for potable water
are not exceeded.
1-45 l/min
2.55 m3/h
10 bar
20 - 75 °C
35 - 60 °C
15