Fig. 34: Cleaning Of The Measuring Turbine; Fig. 35: Circlip - oventrop Regumaq X-45 Operating Instructions Manual

Hide thumbs Also See for Regumaq X-45:
Table of Contents

Advertisement

Regumaq X-45
Troubleshooting
24
4
Fig. 34:
Cleaning of the measuring turbine
4
Fill and drain ball valve for potable water (cold)
5
Volume fl ow sensor for potable water circuit
VTY 20
12
Temperature sensor for potable water (cold)/
circulation S3
24
Union nut heat exchanger side
25
Union nut cold potable water supply
7
Loosen the union nut of the volume fl ow sensor for
potable water circuit VTY 20 (position
page 53) with a 24 mm spanner.
8
Loosen the union nut of the temperature sensor for
potable water (cold)/circulation S3 (position
34 on page 53).
9
Carefully pull the volume fl ow sensor for potable water
circuit VTY 20 (position
the temperature sensor for potable water (cold)/
circulation S3 (position
out of the fi tting.
10
Remove the O-rings and keep them protected against
dirt until they are reinstalled.
11
Loosen the union nut cold potable water supply
25
(position
in Fig. 34 on page 53) with a 38 mm
spanner.
12
Loosen the union nut heat exchanger side (position
24
in Fig. 34 on page 53) with a 37 mm spanner.
13
Carefully remove the fi tting from the station.
NOTICE
Overheating of the measuring turbine!
The bearing of the measuring turbine is cooled by
the water fl ow during operation. The use of
compressed air for cleaning can lead to irreparable
damage due to overheating.
!
Clean the measuring turbine with running water
only.
14
Clean the sleeve with measuring turbine. Remove
residues such as hemp residues with (running) water.
Direct the fl owing water through the fi tting in the
opposite direction to the direction of fl ow (from the
24
direction of position
138114082-V04.04.2022
25
5
12
5
in Fig. 34 on
12
in Fig.
5
in Fig. 34 on page 53) and
12
in Fig. 34 on page 53)
to the direction of position
25
in Fig. 34 on page 53). A water hose with an
appropriate spray nozzle is particularly suitable for this
purpose.
15
Check that the measuring turbine has been cleared of
foreign substances and is running smoothly again.
16
If the cleaning was successful, install the fi tting in the
reverse order of removal.
If the measuring turbine is still blocked, you
must remove the sleeve with measuring
turbine as described in par. 9.4.2.1.
The removed fl at seals are not reusable. Use new
seals for reassembly.
17
Close the lower fi ll and drain ball valve for potable
17
water (hot) (position
in Fig. 1 on page 11
).
18
Vent the potable water circuit (see par. 7.2 on page
29)
19
Restore the power supply.
9.4.2.1
Removal of the measuring turbine
Required tools
Circlip pliers J2 (e.g. EAN 4003773-048534).
1
Loosen the circlip (position
53) with suitable circlip pliers.
Fig. 35:
Circlip
22
Circlip
2
Remove the circlip.
and
in Fig. 33 on page 52
22
in Fig. 35 on page
22
53