Final inspection
1
Has the installation been tested for
leaks (DIN EN 806)?
2
Has the functional check been car-
ried out according to the operating
instructions?
Relay assignment
Relay
Function
R1
R2
R3
R4
R5
Instruction/Handover
The installer has instructed the operator in the function and intended use of the fresh water station.
The installer has advised the operator of the intended operation of potable water installations.
The installer has handed over the necessary documents to the operator.
Information on the intended operation of potable water installations:
- Stagnation must be avoided, regular potable water exchange must be ensured
- TPWH >= 60 °C must be maintained at the hot water outlet
- The circulation system must be designed in such a way that the potable water temperature does not fall below the
station outlet temperature of >= 60 °C by more than 5 K
- TPWC must be maintained at < 25 °C at the cold water outlet
Installer / Installation company
_____________________________________________________________
Date / Signature / Stamp
User
Handover report received
_____________________________________________________________
Date / Signature
¨
¨
¨
¨