Emerson Rosemount 3051SAL Reference Manual page 77

Table of Contents

Advertisement

Reference Manual
00809-0200-4802, Rev BA
Device Status
Description
Pressure has
The sensor has exceeded the
Exceeded Limits
maximum measurement range.
Electronics
The electronics temperature has
Temperature has
exceeded the transmitter's
Exceeded Limits
maximum range.
Supply Voltage Low
The supply voltage is low and may
soon affect broadcast updates.
Database Memory
The device has failed to write to
Warning
the database memory. Any data
written during this time may have
been lost.
Configuration Error
The device has detected a
configuration error based on a
change to the device.
HI HI Alarm
The primary variable has surpassed
the user defined limit.
HI Alarm
The primary variable has surpassed
the user defined limit.
Troubleshooting
Recommended Action
1.
Check process for possible saturation condition
2.
Verify that the appropriate sensor was chosen for the
application
3.
Reconfirm sensor configuration
4.
Reset the device
5.
Replace the sensor
1.
Verify environmental temperature is within the
transmitter's range
2.
Remote mount the transmitter away from process
and environmental conditions
3.
Reset the device
4.
If the condition persists, replace the electronics
1.
Replace the Power Module
1.
Reset the device
2.
Reconfirm all configuration items in the device
3.
If logging dynamic data not needed, this advisory
can be safely ignored
4.
If the condition persists, replace the electronics
1.
Click on details for more information
2.
Correct the parameter that has a configuration error
3.
Reset the device
4.
If the condition persists, replace the electronics
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
Section 6: Troubleshooting
May 2013
69

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount 3051shpRosemount 3051s

Table of Contents