Emerson Rosemount 3051SAL Reference Manual page 73

Table of Contents

Advertisement

Reference Manual
00809-0200-4802, Rev BA
Operation and Maintenance
Diagnostic Button Screen 7.1: the terminal voltage
has dropped below level of operating limit. Replace
s u p l y
the Power Module
(Part Number: 00753-9220-0001)
f a i l u r
Diagnostic Button Screen 7.2: the terminal voltage
is below the recommended operating range - if this is
s u p l y
a battery operated device, the Power Module should
be replaced - for line powered devices, the supply
voltage should be increased
l o w
Diagnostic Button Screen 8: the device may not be
able to communicate with the radio or the radio has
r a d i o
an internal error. In this state the device may still be
operational and publishing HART data
f a i l u r
Diagnostic Button Screen 9.1: configuration of the
transmitter is invalid such that critical operation of
c o n f g
the device may be affected - check the extended
configuration status to identify which configuration
item(s) need to be corrected
f a i l u r
Diagnostic Button Screen 9.2: configuration of the
transmitter is invalid such that non-critical operation
c o n f g
of the device may be affected - check the extended
configuration status to identify which configuration
item(s) need to be corrected
w a r n
Section 5: Operation and Maintenance
May 2013
65