ABB PVS-100-TL-B-SY2 Product Manual page 88

Table of Contents

Advertisement

Three topologies of ethernet connection to the router are available:
The ring configuration is the preferrable way to connect the units in order to allow reaching
inverters in case of single inverter fault.
In case inverters are connected to the networking switch with a ring topology is recommended
to enable SPT protocol on the switch (Spanning Tree Protocol SPT (IEEE 802.1D) is enabled
by default on inverters).
On each configuration of connection the maximum length of the cable
must be 100m maximum between inverter – inverter and inverter –
switch.
For further information on the Ethernet connection refer to the Local Area Network standard
IEEE802.3.
Please refer to Aurora Vision documents available on ABB website for further information
how to get an Aurora Vision account for remotely monitoring and managing the installed solar
assets.
No initial setup is required to start data transmission to Aurora Vision.
Internet connection is required to use all the Aurora Vision remote functionalities.
Ring configuration
Daisy chain configuration
Star configuration
- 88 -
5 - Installation
ROUTER
ROUTER
ROUTER