Commissioning
Preparing the device address setting via the PROFIBUS or the RS 232
diagnostic interface
If you set the rotary switches to a value between "7Eh" and "FEh", the device is
allocated the address "7Eh" (126), which you can modify during operation via the
PROFIBUS or the RS 232 diagnostic interface. The new address is stored in the
volatile memory.
If you set the rotary switches to "FFh", the factory preset address 126 is selected.
You can modify the address during operation via the PROFIBUS or the RS 232
diagnostic interface. The new address is stored in the non-volatile memory, which
means the modified address becomes valid when the device is switched off and
back on again.
1. Set the rotary switches to "7Eh" ... "FEh" or "FFh".
2. Switch the device off and back on again or restart via the RS 232 diagnostic
interface using the RS<CHK><ETX> command so that the PROFIBUS
adopts the device address.
Setting the device address via the PROFIBUS
The device supports the PROFIBUS service "Set_Slave_Add" via the Service
Access Point SAP55 of a DP slave. You will require a DPM2 master here.
You must set the address using a suitable projecting tool (e.g. Siemens "STEP7 /
SIEMATIC Manager" or VAZ-PB-SIM "PROFIBUS DP Master Simulator").
Setting the device address using the Siemens "STEP7 / SIMATIC
Manager"
1. To assign the PROFIBUS interface parameterization to the "S7ONLINE" ac-
cess point, select "Options", "Set PG/PC interface ..." and "PC adapter
(PROFIBUS)" from the SIMATIC Manager menu.
2. To allocate the address, select "Target system", "PROFIBUS" and "Allocate
PROFIBUS address ..." from the HW Config menu and enter or select the
PROFIBUS address. Press "OK" to change the address.
Setting the device address using the VAZ-PB-SIM "PROFIBUS DP
Master Simulator"
1. Select "Address" and "Modify address of PROFIBUS slave ..." from the menu.
2. Enter the old and new address.
3. Press "OK" to change the address.
Setting the device address via the RS 232 diagnostic interface
1. Set the device address (<Addr> = "00" ... "7D") using the "Set device address"
command SD<Addr><CHK><ETX>.
2. Use the "Get address" command GA<CHK><ETX> to view the current
address setting.