Installation
5.1
Unpacking
Check the product for damage while unpacking. In the event of damage to the
product, inform the post office or parcel service and notify the supplier.
Check the package contents with your purchase order and the shipping
documents for:
Retain the original packaging in case you have to store or ship the device again at
a later date.
Should you have any questions, please contact Pepperl+Fuchs.
5.2
EMC concept
The outstanding noise immunity of the IDENTControl Compact against emission
and immission is based on its consistent shielding design, which uses the
principle of the Faraday cage. Interference is caught in the shield and safely
diverted via the ground connections.
Read head
The cable shielding is used to discharge electromagnetic interference. When
shielding a cable, you must connect both sides of the shield to ground with low
resistance and low inductance.
Note!
If cables with double shields are used, e.g. wire mesh and metalized foil, the both
shields must be connected together, with low resistance, at the ends when
making up the cable.
Power supply cables are the source of much interference, e.g. from the supply
lines of 3-phase electric motors. For this reason, the parallel laying of power
supply cables with data and signal cables should be avoided, particularly in the
same cable duct.
The metal enclosure of the IDENTControl Compact and the metal enclosure of the
R/W heads complete the consistent shielding concept.
Delivery quantity
Device type and version in accordance with the type plate
Accessories
Quick start guide
IDENTControl
PROFIBUS
PLC