Figure 2-5, Battery Hardware Installation; Figure 2-6, Inverter Dc Hardware Installation; Table 2-2, Dc Wire Size For Increased Distance - Magnum Energy MagnaSine Hybrid Owner's Manual

Renewable energy pure sine wave inverter/charger
Table of Contents

Advertisement

Table 2-2, DC Wire Size For Increased Distance

Inverter
5 feet or less
Model
In Conduit
#4/0 AWG
MSH4024RE
(107.2mm²)
* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F)
2.4.3
DC Cable Connections
Do not put anything between the battery cable ring lug and the battery post or the fl at metal part
of the inverter's DC terminal. When connecting the battery cable to the battery post or inverter
DC terminal, the cable should be placed directly against the inverter terminal or battery post.
Incorrectly installed hardware causes a high resistance connection which could lead to poor inverter/
charger performance, and may melt the cable and terminal connections.
Refer to Figures 2-5 and 2-6 to connect the DC cables and to stack the hardware correctly. Tighten
the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).
CAUTION: The DC terminal and Flange/Kep nuts are made of stainless steel which have
a high likelihood of seizure. To help prevent the bolt and nut from seizing—causing the
bolts to strip or snap/break-off—the use of anti-seize lubricant is highly recommended.
Info: If antioxidant grease or spray is used, apply it after all the connections have been
made and are properly tightened.
Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Flange/Kep nuts.
nut
split washer
flat washer
CAUTION:
Ensure nothing is
placed between
the cable ring lug
and battery post.
Figure 2-5, Battery Hardware
Installation
© 2013 Magnum Energy, Inc.
Minimum Recommended DC Wire Size (one way)*
In Free Air
In Conduit
#4/0 AWG
#2/0 AWG
(107.2mm²)
(67.4mm²)
Battery
Temperature
Sensor
battery cable
(with ring lug)
battery
post
5 to 10 feet
In Free Air
#4/0 AWG
(107.2mm²)
x2
Inverter DC terminal
(
5/16–18 bolt,
5/8" usable length
battery cable
(with ring lug)
Figure 2-6, Inverter DC Hardware
Installation
Installation
10 to 15 feet
In Conduit
In Free Air
#4/0 AWG
not
(107.2mm²)
recommended
x2
CAUTION:
Ensure nothing is
placed between the DC
terminal and ring lug.
5/16-18
Flange or
Kep nut
)
Page 15