Protection Circuitry Operation; Table 3-1, Inverter Battery Turn On/Off Levels - Magnum Energy MagnaSine Hybrid Owner's Manual

Renewable energy pure sine wave inverter/charger
Table of Contents

Advertisement

3.6

Protection Circuitry Operation

The inverter is protected against fault conditions and in normal usage it will be rare to see any.
However, if a condition occurs that is outside the inverter's normal operating parameters, then
it will shut down and attempt to protect itself, the battery bank, and your AC loads. If there is a
condition that causes the inverter to shut down, it may be one of the following conditions [also
refer to the Troubleshooting section (Section 4.2) to help diagnose and clear the fault condition].
Low Battery – The inverter will shut off whenever the battery voltage falls to the LBCO (Low
Battery Cut Out) level to protect the batteries from being over-discharged. After the inverter
has reached the LBCO level and turned off, the inverter will automatically restart after one of
the following conditions:
1. AC power is applied and the inverter begins operating as a battery charger.
2. Battery voltage rises to the LBCI (Low Battery Cut In) level.
The inverter's status LED turns off when a low battery fault condition occurs. Refer to Table
3-1 to determine the LBCO and LBCI levels for your inverter model.
High Battery – In the event the battery voltage approaches the HBCO (High Battery Cut
Out) level, the inverter will automatically shut down to prevent the inverter from supplying
unregulated AC output voltage. The inverter's status LED turns off when a high battery fault
condition occurs. The inverter will automatically restart when the battery falls to the HBCI
(High Battery Cut In) level. Refer to Table 3-1 to determine the HBCO and HBCI levels for
your inverter model.
Info: High battery voltage may be caused by excessive or unregulated voltage from
the solar panels or other external charging sources.
Overload – During inverter and standby operation, the inverter monitors the DC and AC
current levels. In the event of a short-circuit or an overload condition for more than a few
seconds, the inverter will shut down. To start operating after this fault, the inverter must be
restarted (turned back on) once the inverter's AC loads are reduced/removed.
Over-temperature – If internal power components begin to exceed their safe operating
temperature level, the inverter will shut down to protect itself from damage. The inverter's
status LED turns off to indicate the over-temperature fault condition. The inverter automatically
restarts after the unit cools down.
Internal Fault – The inverter continually monitors several internal components and the
processor communications. If a condition occurs that does not allow proper internal operation,
the inverter will shut down to protect itself and the connected loads. The inverter will need
to be reset to start operating—refer to Section 4.3 for information on resetting the inverter.

Table 3-1, Inverter Battery Turn On/Off Levels

© 2013 Magnum Energy, Inc.
Inverter battery
turn ON/OFF Levels
HBCO
HBCI
LBCI
LBCO*
(1 minute delay)
LBCO (immediate)
*adjustable with remote control
Inverter Model
MSH4024RE
>33.8 VDC
33.2 VDC
25.0 VDC
20.0 VDC
(18.0 - 24.4 VDC)
17.0 VDC
Operation
Page 37

Advertisement

Table of Contents
loading

This manual is also suitable for:

Msh4024re

Table of Contents