Figure 2-5, Battery Hardware Installation; Figure 2-6, Inverter Dc Hardware Installation; Table 2-2, Dc Wire Size For Increased Distance - Magnum Energy ME Series Owner's Manual

Me series modifi ed sine wave inverter/chargers
Hide thumbs Also See for ME Series:
Table of Contents

Advertisement

Table 2-2, DC Wire Size For Increased Distance (in free air)
Inverter
Model
ME2000
ME2012
ME2512
ME3112
* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).
2.4.3
DC Cable Connections
Do not put anything between the DC cable ring lug and the battery terminal post or the fl at metal
part of the inverter's DC terminal. When connecting the DC cable to the battery or inverter DC
terminals, the cable should be placed directly against the inverter or battery terminals. Incorrectly
installed hardware causes a high resistance connection, which could lead to poor inverter/charger
performance and may melt the cable and terminal connections.
Follow the examples in Figures 2-5 and 2-6 to connect the DC cables and stack the hardware
correctly. Tighten the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).
CAUTION: The DC terminal and Kep nuts are made of stainless steel, which has a high
likelihood of seizure. To help prevent the bolt and nut from seizing — causing the bolts
to strip or snap/break-off — the use of anti-seize lubricant is highly recommended.
Info: If antioxidant grease or spray is used, apply it after all the connections have been
made and are properly tightened.
Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Kep nuts.
nut
split
washer
flat
washer
battery cable
(with ring lug)
CAUTION:
Ensure nothing is
placed between
the cable ring lug and
the battery post.
Figure 2-5, Battery Hardware
Installation
© 2010 Magnum Energy, Inc.
Minimum Recommended DC Wire Size (one way)
1-3 feet
#2/0 AWG (67.4 mm
)
2
#2/0 AWG (67.4 mm
)
2
#4/0 AWG (107.16 mm
)
2
#4/0 AWG (107.16 mm
)
2
Battery
Temperature
Sensor
battery
post
3-5 feet
#4/0 AWG (107.16 mm
)
2
#4/0 AWG (107.16 mm
)
2
#4/0 AWG (107.16 mm
)
2
#4/0 AWG (107.16 mm
)
2
Inverter DC
terminal
(5/16 -18"
bolt,
5/8" length)
battery
cable (with
ring lug)
Figure 2-6, Inverter DC Hardware
Installation
*
5-10 feet
#4/0 AWG (107.16 mm
)
2
#4/0 AWG (107.16 mm
)
2
#4/0 AWG (107.16 mm
)
2
consult code
CAUTION:
Ensure nothing is
placed between
the DC terminal
and the ring lug.
5/16 -18"
Flange or
Kep nut
Installation
Page 16