Mounting The Inverter; Figure 2-2, Approved Mounting Positions - Magnum Energy MagnaSine Hybrid Owner's Manual

Renewable energy pure sine wave inverter/charger
Table of Contents

Advertisement

2.2

Mounting the Inverter

The inverter base can reach a temperature up to 90°C (194°F) and should be mounted on a
noncombustible surface*. This surface and the mounting hardware must also be capable of
supporting at least twice the weight of the inverter. To meet regulatory requirements, the MSH-RE
Series must be mounted in one of the following positions (as shown in Figure 2-2):
above or under a horizontal surface (shelf or table),
on a vertical surface (wall) with the DC terminals to the right,
on a vertical surface (wall) with the DC terminals toward the bottom, the MP-HOOD (inverter
hood) installed on the top, and either the ME-CB or MPX-CB (Conduit boxes) or MMP Series
(single inverter enclosure) installed on the inverter's bottom.
Info: The ME-CB, MPX-CB, and the MMP Series enclosure prevent material from falling
out the bottom in the event of an internal fi re, and also allow suffi cient ventilation to
prevent the inverter from overheating under normal operating conditions. The MP-HOOD
inverter hood helps prevent items from falling inside—causing damage to the inverter.
Info: Magnum provides a backplate for mounting the inverter. The backplate (PN: BP-S
single plate) also accommodates the mounting of the MMP Series enclosure.
After determining the mounting position, refer to the physical dimensions as shown in Figure
2-3, or use the base of the inverter as a template to mark your mounting screw locations. After
marking the mounting screw locations, mount the unit with appropriate mounting hardware.
* Noncombustible surface – A surface made of material that will not ignite, burn, support combustion, or
release fl ammable vapors when subjected to fi re or heat as per the ASTM E136 standard. For the most part,
these are materials that are largely comprised of inorganic materials such as stone, steel, iron, brick, tile,
concrete, slate, and glass. Avoid common building materials such as gypsum board as well as paint, wall
coverings, and any type of wood.
30
S
HELF OR
M
OUNTED
(
RIGHT SIDE UP
W
ALL
(DC
TERMINALS TO THE RIGHT
© 2013 Magnum Energy, Inc.
T
ABLE
)
M
OUNTED
)

Figure 2-2, Approved Mounting Positions

S
T
M
HELF OR
ABLE
OUNTED
(
)
UP SIDE DOWN
Installation
W
M
ALL
OUNTED
(DC
TERMINALS
*)
FACING DOWN
*W
HEN THE INVERTER
IS MOUNTED IN THIS
,
MP-HOOD
POSITION
THE
(
)
INVERTER HOOD ON TOP
ME-CB/
AND EITHER THE
MPX-CB (
CONDUIT BOX
)
MMP
ON BOTTOM
OR
S
E
ERIES
NCLOSURE MUST
.
BE USED
Page 9