Installation
Table 2-2, DC Wire Size For Increased Distance
Inverter Model
MSH3012M
MSH4024M
* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F) in free air.
2.4.3
DC Cable Connections
Do not put anything between the battery cable ring lug and the battery post or the fl at metal part
of the inverter's DC terminal. When connecting the battery cable to the battery post or inverter
DC terminal, the cable should be placed directly against the inverter terminal or battery post.
Incorrectly installed hardware causes a high resistance connection which could lead to poor inverter/
charger performance, and may melt the cable and terminal connections.
Refer to Figures 2-5 and 2-6 to connect the DC cables and to stack the hardware correctly. Tighten
the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).
CAUTION: The DC terminal and Flange/Kep nuts are made of stainless steel which have
a high likelihood of seizure. To help prevent the bolt and nut from seizing—causing the
bolts to strip or snap/break-off—the use of anti-seize lubricant is highly recommended.
Info: If antioxidant grease or spray is used, apply it after all the connections have been
made and are properly tightened.
Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Flange/Kep nuts.
nut
split washer
flat washer
CAUTION:
Ensure nothing is
placed between
the cable ring lug
and battery post.
Figure 2-5, Battery Hardware
Installation
Page 15
Minimum Recommended DC Wire Size (one way)*
5 feet or less
#4/0 AWG
(107.2 mm
)
2
#2/0 AWG
(67.4 mm
)
2
Battery
Temperature
Sensor
battery cable
(with ring lug)
battery
post
5 to 10 feet
#4/0 AWG
(107.2 mm
) x2
2
#4/0 AWG
(107.2 mm
)
(107.2 mm
2
placed between the DC
Inverter DC terminal
(
5/16–18 bolt,
)
5/8" usable length
battery cable
(with ring lug)
Figure 2-6, Inverter DC Hardware
Installation
© 2013 Magnum Energy, Inc.
10 to 15 feet
not
recommended
#4/0 AWG
) x2
2
CAUTION:
Ensure nothing is
terminal and ring lug.
5/16-18
Flange or
Kep nut