Figure 2-5, Battery Hardware Installation; Figure 2-6, Inverter Dc Hardware Installation; Table 2-2, Dc Wire Size For Increased Distance - Magnum Energy RD Series Owner's Manual

Modified sine wave inverter/chargers
Hide thumbs Also See for RD Series:
Table of Contents

Advertisement

Table 2-2, DC Wire Size For Increased Distance (in free air)
Inverter
Model
RD2212
#4/0 AWG (107.16 mm
RD1824
#2/0 AWG (67.4 mm
RD2824
#4/0 AWG (107.16 mm
RD3924
#4/0 AWG (107.16 mm
* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).
2.4.3
DC Cable Connections
Do not put anything between the DC cable ring lug and the battery terminal post or the fl at metal
part of the inverter's DC terminal. When connecting the DC cable to the battery or inverter DC
terminals, the cable should be placed directly against the inverter or battery terminals. Incorrectly
installed hardware causes a high resistance connection, which could lead to poor inverter/charger
performance and may melt the cable and terminal connections.
Follow the examples in Figures 2-5 and 2-6 to connect the DC cables and stack the hardware
correctly. Tighten the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).
CAUTION: The DC terminal and Kep nuts are made of stainless steel, which has a high
likelihood of seizure. To help prevent the bolt and nut from seizing — causing the bolts
to strip or snap/break-off — the use of anti-seize lubricant is highly recommended.
Info: If antioxidant grease or spray is used, apply it after all the connections have been
made and are properly tightened.
Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Kep nuts.
nut
split
w asher
flat
w asher
battery cable
(w ith ring lug)
C A U T ION:
Ensure nothing is
placed betw een
the cable ring lug
and the battery
post.
battery
post
Figure 2-5, Battery Hardware
Installation
© 2010 Magnum Energy, Inc.
Minimum Recommended DC Wire Size (one way)
1-3 feet
)
#4/0 AWG x2 (107.16 mm
2
)
#2/0 AWG (67.4 mm
2
)
#4/0 AWG (107.16 mm
2
)
#4/0 AWG x2 (107.16 mm
2
Battery
T em perature
Sensor
3-5 feet
)
2
)
#4/0 AWG (107.16 mm
2
)
#4/0 AWG x2 (107.16 mm
2
)
2
Inverter D C
term inal
(5/16 -18" bolt,
5/8" length)
battery cable
(w ith ring lug)
Figure 2-6, Inverter DC Hardware
Installation
Installation
*
5-10 feet
not recommended
)
2
)
2
not recommended
C A U T ION:
Ensure nothing is
placed betw een
the D C term inal
and the ring lug.
5/16 -18"
F lange or
Kep nut
Page 16