Installation

Table 2-2, DC Wire Size For Increased Distance

Inverter
5 feet or less
Model
In Conduit
MS2012
#4/0 AWG
MS2812
#4/0 AWG
MS4024
#4/0 AWG
* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).
2.4.3
DC Cable Connections
Do not put anything between the DC cable ring lug and the battery terminal post or the fl at metal
part of the inverter's DC terminal. When connecting the DC cable to the battery or inverter DC
terminals, the cable should be placed directly against the inverter or battery terminals. Incorrectly
installed hardware causes a high resistance connection which could lead to poor inverter/charger
performance and may melt the cable and terminal connections.
Follow fi gures 2-5 and 2-6 on how to connect the DC cables and stack the hardware correctly.
Tighten the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 N-m).
CAUTION: The DC terminal and Kep nuts are made of stainless steel which have a high
likelihood of seizure. To help prevent the bolt and nut from seizing - causing the bolts
to strip or snap/break-off - the use of anti-seize lubricant is highly recommended.
Info: If antioxidant grease or spray is used, apply it after all the connections have
been made and are properly tighten.
Info: A ½-inch wrench or socket is used to tighten the 5/16-18 SAE Kep nuts.
nut
split w asher
flat w asher
battery cable
(w ith ring lug)
C A U T ION:
Ensure nothing is
placed betw een
cable ring lug and
battery post.
Figure 2-5, Battery Hardware
Installation
Page 16
Minimum Recommended DC Wire Size (one way)*
In free air
In Conduit
#2/0 AWG
#4/0 AWG x2
#4/0 AWG
#4/0 AWG x2
#2/0 AWG
#4/0 AWG x2
Battery
T em perature
Sensor
battery
post
5 to 10 feet
In free air
#4/0 AWG
#4/0 AWG x2
#4/0 AWG
Inverter D C
term inal
(5/16 -18 bolt,
5/8" length)
battery cable
(w ith ring lug)
Figure 2-6, Inverter DC Hardware
Installation
© 2009 Magnum Energy Inc
10 to 15 feet
In Conduit
In free air
not
#4/0 AWG x2
recommended
not
not
recommended
recommended
not
#4/0 AWG x2
recommended
C A U T ION:
Ensure nothing is
placed betw een
D C term inal
and ring lug.
5/16 -18
Kep nut