Do you have a question about the ME Series and is the answer not in the manual?
Questions and answers
J, R. Potter
February 13, 2025
Unit is not sending battery AC power to interior circuits.
1 comments:
Mr. Anderson
February 13, 2025
The Magnum Energy ME Series unit may not be sending battery AC power to interior circuits because it is in standby mode, where it monitors for acceptable AC voltage from an external source before activating the AC transfer relay. If no AC source is connected or the voltage is not acceptable, the relay remains open, preventing power transfer. Additionally, issues such as a tripped AC input circuit breaker, incorrect wiring, or battery-related problems could also cause this issue.
Restrictions on Use The ME Series Inverter/Charger may only be used in life-support devices or systems with the express written approval of Magnum Energy. Failure of the ME Series Inverter/Charger can reasonably be expected to cause the failure of that life-support device or system, or to affect the safety or effectiveness of that device or system.
Page 6
Figure 2-7, Battery Temperature Sensor ..................17 Figure 2-8, ME Series Inverter/Charger - AC Wiring ................ 20 Figure 2-9, ME Series Inverter/Charger - AC Wiring (Access Cover) ..........20 Figure 2-10, AC Terminal Block ..................... 21 Figure 2-11, AC Wiring for Single In - Single Out (30 A) Confi gurations ..........24 Figure 2-12, AC Wiring for Single In - Single Out (60 A) Confi...
Introduction 1.0 Introduction Congratulations on your purchase of the ME Series inverter/charger from Magnum Energy. The ME Series is a modifi ed sine wave inverter designed especially for mobile applications. Powerful, yet simple to operate, this inverter/charger will provide you with the years of trouble-free performance you have come to expect from Magnum Energy, all backed by our limited 3 year warranty.
The front of the ME Series is equipped with the following features (see Figures 1-1 and 1-2): Power ON/OFF Switch - a momentary pushbutton switch that alternately turns the inverter On or Off.
Introduction The left side of the ME Series is equipped with the following features (see Figure 1-3): Exhaust Air Vent - ventilation openings that allow heated air to be removed by the internal cooling fan. Model/Serial Number Label - includes model/serial number information, date of manufacture, and inverter and charger specifi...
Even though it is diffi cult to calculate exactly how long an inverter will run a particular appliance, the best advice is trial and error. Your ME Series inverter has a built-in safeguard that automatically protects your batteries from over-discharge.
If items appear to be missing or damaged, contact your authorized Magnum Energy dealer or Magnum Energy. If at all possible, keep your shipping box. It will help protect your inverter from damage if it ever needs to be returned for service. Save your proof-of-purchase as a record of your ownership;...
Page 15
Do not install this inverter in any area that contains extremely fl ammable liquids like gasoline or propane, or in locations that require ignition-protected devices. WARNING: The ME Series inverter/charger is not ignition-protected and may not be located in an engine compartment with gasoline fueled engines under any circumstances.
This surface and the mounting hardware must also be capable of supporting at least twice the weight of the inverter. To meet regulatory requirements, the ME Series must be mounted in one of the following positions, as shown in Figure 2-2: •...
Installation Wiring the Inverter - General Requirements This section describes the requirements and recommendations for wiring the ME Series inverter/ charger. Before wiring the inverter/charger, read all instructions. All wiring should meet all local codes and industry standards, and be performed by qualifi...
3) the correct DC voltage and polarity have been verifi ed. Info: For the ME Series inverter/charger to perform optimally, a minimum battery bank of 200 AH is recommended for moderate loads (<1000W) and greater than 400 AH for heavy loads (≥1000W).
AC circuits. The ME Series allows the AC input and output wiring to be permanently wired. The inverter’s input is wired to the service/distribution panel (main panel). The inverter’s output is then wired to a dedicated panel (sub-panel) .
Page 35
2.5.7 AC Conductor Wiring (ME2000 models) The ME2000 is a new model in the ME Series family. It offers a cost-effective alternative to the ME2012 while still providing the same features. This model has a slightly smaller height, but otherwise has the same footprint as the other ME Series inverters. The ME2000 can be wired in a single in - single out confi...
The ME Series inverter/charger uses both AC and DC power; however, the AC electrical system is isolated from the DC electrical system by an internal transformer. Although this inverter/charger has two electrical systems, each must be properly grounded and connected to a common point.
Page 40
(see Figure 2-18). The DC ground terminal on the ME Series must also be connected to the boat’s safety ground bus. This ensures that both the inverter’s AC and DC ground terminals are connected to the boat’s safety ground bus as a safety measure to provide protection against faults, and to provide a path for AC fault currents while the boat is connected to shore power.
AC source (e.g., shore power or a generator) is qualifi ed, another neutral-to-ground connection is introduced in the system. When the ME Series is connected to this external AC source and goes into Standby Mode, the internal relay automatically opens the neutral-to-ground connection, as shown in Figure 2-19.
Reverse the removed bolt, and place it back terminal bolt/nut, in the chassis hole to attach a correctly sized reversed and ground cable to the ME Series chassis, as tightened shown in Figure 2-20. Place the washer and nut on the bolt, over...
5 to 50 watts using the ME-RC50 remote display. Inverting - When a load greater than 5 watts is connected to the inverter output, the ME Series “inverts” the DC power from the battery and supplies 120 VAC power to your sub-panel. The inverter’s green LED fl...
Operation Standby Mode The ME Series features an automatic transfer relay and an internal battery charger when operating in Standby Mode. Standby Mode begins whenever AC power (shore power or generator) is connected to the inverter’s AC input. Once the AC voltage and frequency of the incoming AC power is within the AC input limits, an automatic AC transfer relay is activated.
Info: If the battery voltage falls to the re-bulk voltage (12.1 VDC) or lower, the unit will begin another bulk charge. * These settings in the ME Series are changeable and leave the factory with default values (see Table 3-2, Inverter/Charger Default Values). These default values are adequate for most installations, however, if you determine that some of the values need to be changed for your particular system, the ME-RC50 remote control may be purchased to adjust these settings.
The transfer from Standby Mode to Inverter Mode occurs in approximately 16 milliseconds. While the ME Series is not designed as a computer UPS system, this transfer time is usually fast enough to hold them up. However, the VAC dropout setting has an effect on the ability of the loads to transfer without resetting.
Operation Factory Default Values Your ME Series inverter/charger uses default values for the adjustable settings (see Table 3-2) that are adequate for most installations. If some of your operating parameters need to be changed from the default values, the optional ME-RC50 remote control can be used to make those changes. To help you determine if you need the ME-RC50 remote display, information on the inverter/charger settings that can be changed is provided below.
Maintenance and Troubleshooting 4.0 Maintenance and Troubleshooting The following information is provided to help you keep your ME Series inverter/charger in optimum operational condition. Recommended Inverter and Battery Care The ME Series inverter/charger is designed to provide you with years of trouble-free service.
Maintenance and Troubleshooting Troubleshooting The ME Series inverter/charger is a fairly simple device to troubleshoot. There are only two active circuits (AC and DC) as well as a charging circuit. The following chart is designed to help you quickly pinpoint the most common inverter failures.
Appendix A - Specifi cations A-2 Optional Equipment and Accessories The following Magnum Energy components are available for use with the ME Series inverter/charger. Some of these items are required depending upon the intended use of the inverter. MMP Series Enclosures The MMP175-30D.
AC shore power or generator power. Info: For the ME Series inverter/charger to perform optimally, a minimum battery bank of 200 AH is recommended for moderate loads (<1000W) and greater than 400 AH for heavy loads (≥1000W).
Magnum Energy’s limit of liability under the limited warranty shall be the actual cash value of the product at the time the original purchaser returns the product for repair, determined by the price paid by the original purchaser. Magnum Energy shall not be liable for any other losses or damages.
Page 62
Magnum Energy, Inc. 2211 West Casino Rd. Everett, WA 98204 Phone: 425-353-8833 Fax: 425-353-8390 Web: www.magnumenergy.com ME Series Owner’s Manual (PN: 64-0002 Rev A)
Need help?
Do you have a question about the ME Series and is the answer not in the manual?
Questions and answers
Unit is not sending battery AC power to interior circuits.
The Magnum Energy ME Series unit may not be sending battery AC power to interior circuits because it is in standby mode, where it monitors for acceptable AC voltage from an external source before activating the AC transfer relay. If no AC source is connected or the voltage is not acceptable, the relay remains open, preventing power transfer. Additionally, issues such as a tripped AC input circuit breaker, incorrect wiring, or battery-related problems could also cause this issue.
This answer is automatically generated