Figure 2-9, Battery Hardware Installation; Figure 2-10, Inverter Dc Hardware Installation; Table 2-4, Dc Wire Size For Increased Distance - Magnum Energy MS-PAE Series Owner's Manual

Pure sine wave inverter / charger
Table of Contents

Advertisement

MS4024PAE
MS3748PAEJ
& MS4448PAE
* Copper wire rated with 90°C (194°F) insulation at an ambient temperature of 30°C (86°F).
2.3.3 DC Cable Connections
Do not put anything between the DC cable ring lug and the battery terminal post or the fl at metal
part of the inverter's DC terminal. When connecting the DC cable to the battery or inverter DC
terminals, the cable should be placed directly against the inverter or battery terminals. Incorrectly
installed hardware causes a high resistance connection which could lead to poor inverter/charger
performance and may melt the cable and terminal connections.
Follow fi gures 2-9 and 2-10 on how to connect the DC cables and stack the hardware correctly.
Tighten the terminal connections from 10 to 12 ft lbf (13.6 to 16.3 Nm).
CAUTION: The DC terminal bolt and nut are made of stainless steel which have a high
likelihood of seizure. To help prevent the bolt and nut from seizing - causing the bolt to
strip or snap/break-off - the use of anti-seize lubricant is highly recommended.
Info: If antioxidant grease or spray is used, apply it after all the connections have been
made and are properly tighten.
Info: A 1/2-inch wrench or socket is used to tighten the 5/16 SAE Flange or Kep nuts.
NUT
SPLIT WASHER
FLAT WASHER
BATTERY CABLE
(
)
WITH RING LUG
CAUTION:
E
NSURE NOTHING IS
PLACED BETWEEN
THE CABLE RING LUG
.
AND BATTERY POST
BATTERY
POST
Figure 2-9, Battery Hardware
Installation
© 2009 Magnum Energy Inc.

Table 2-4, DC Wire Size For Increased Distance

Minimum Recommended DC Wire Size (one way)*
5 ft or less
#2/0 AWG x 2
#2/0 AWG
BATTERY
TEMPERATURE
SENSOR
5 to 10 ft
#4/0 AWG x 2
#4/0 AWG
I
DC
NVERTER
TERMINAL
(5/16 - 18"
,
BOLT
5/8"
)
LENGTH
BATTERY CABLE
(
)
WITH RING LUG
Figure 2-10, Inverter DC Hardware
Installation
Installation
10 to 15 ft
not recommended
#4/0 AWG x 2
CAUTION:
E
NSURE NOTHING IS PLACED
DC
BETWEEN THE
TERMINAL
.
AND RING LUG
5/16 - 18"
F
LANGE OR
K
EP NUT
Page 19