Transfer Time; Battery Temperature Sensor Operation; Figure 3-10, Bts Temperature To Charge Voltage Change - Magnum Energy MagnaSine Hybrid Owner's Manual

Renewable energy pure sine wave inverter/charger
Table of Contents

Advertisement

Operation
3.4

Transfer Time

While in Standby mode, the AC input is continually monitored. Whenever AC power falls below
the VAC dropout voltage (80 VAC, default setting), the inverter automatically transfers back to
Inverter mode with minimum interruption to your appliances—as long as the inverter is turned
on. The transfer from Standby mode to Inverter mode occurs in approximately 16 milliseconds.
While the MSH-RE Series is not designed as a computer UPS system, this transfer time is usually
fast enough to hold them up. However, the VAC dropout setting has an effect on the ability of the
loads to transfer without resetting. The lower this setting, the longer the effective transfer will be
and therefore, the higher the probability for the output loads to reset. This occurs because the
incoming AC voltage is allowed to fall to a level that is so low that when the transfer does occur,
the voltage on the inverter's output has already fallen low enough to reset the loads.
The disadvantage of a higher VAC dropout setting is that smaller generators (or large generators
with an unstable output) may nuisance transfer. This commonly happens when powering loads that
are larger than the generator can handle—causing the generator's output voltage to constantly
fall below the inverter's input VAC dropout threshold.
Info: When switching from Inverter mode to Standby mode, the inverter waits
approximately 15 seconds to ensure the AC source is stable before transferring.
3.5

Battery Temperature Sensor Operation

The plug-in Battery Temperature Sensor (BTS) is used to determine the battery's temperature.
This information allows the multi-stage battery charger to automatically adjust the battery charge
voltages for optimum charging performance and longer battery life.
With a BTS installed, if the temperature around the BTS is below 77°F (25°C) the absorb and fl oat
charge voltage increases, and if the temperature around the BTS is higher than 77°F (25°C), the
absorb and fl oat charge voltage decreases. See Figure 3-10 to determine how much the charge
voltage changes (increases or decreases) depending on the temperature reading of the BTS. For
example, the nominal absorb charge voltage for a fl ooded battery at 77°F (25°C) on a 24-volt
model is 29.2 VDC. If the battery temperature is 95°F (35°C), the absorb charge voltage would
decrease to 28.6 VDC (29.2 VDC - 0.6 change).
If the temperature sensor is NOT installed, the charge voltages will not be compensated and charges
at a temperature of 77°F (25°C). The life of the batteries may be reduced if they are subjected
to large temperature changes when the BTS is not installed.
Info: When the BTS is connected, the battery charger uses a value of -5mV/°C/Cell
from 0-50°C to change the charge voltage based on temperature.

Figure 3-10, BTS Temperature to Charge Voltage Change

Page 36
Temperature Compensation using BTS
0.75
0.6
0.45
0.3
0.15
0
-0.15
-0.3
-0.45
-0.6
-0.75
0C
0
5C
5
10C
10
15C
15
20C
20
32F
41F
50F
59F
68F
Temperature reading from BTS
no BTS
connected
25C
25
30C
30
35C
35
40C
40
45C
45
50C
77F
86F
95F
104F
113F
122F
© 2013 Magnum Energy, Inc.
24VDC units
+1.5V
+1.2V
+0.9V
+0.6V
+0.3V
No Change
-0.3V
-0.6V
-0.9V
-1.2V
-1.5V
50

Advertisement

Table of Contents
loading

This manual is also suitable for:

Msh4024re

Table of Contents