Appendix D: FACP with Keltron

The following figure illustrates the connections between the FACP and Keltron
Receiver/Transmitter.
CAUTION:
!
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON
MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND MODULE
MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
8th Edition Only
Sprinkler
Supervisory Signal
MS-9600LS Series Manual — P/N 52646:B2 2/12/2010
POSSIBLE EQUIPMENT DAMAGE
Tip
Telephone Line
Ring
Earth
UL Listed
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in their actual
positions in order to clarify wiring connections)
Figure D.1 Wiring to Keltron Printer
Tip
Ring
Earth
UL Listed
8th Edition Only
Alarm/Trouble Signal
4XTMF Module
To Central/
Remote
Station
To Power
Supply
*Note: For more
information, refer to
Keltron manual.
24 VDC
nonresettable power