Appendix D: Facp With Keltron - Honeywell Fire-Lite Alarms MRP-2001 Instruction Manual

Pre-action/deluge control panel
Table of Contents

Advertisement

Appendix D: FACP with Keltron

The following figure illustrates the connections between the FACP and Keltron
Receiver/Transmitter.
CAUTION:
!
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON
MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND MODULE
MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE.
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20
feet and enclosed within conduit or equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1. Terminals 7 and 8: Remote station alarm/trouble inputs.
2. Terminals 9 and 10: Sprinkler supervisory input.
118
OBSERVE CORRECT TERMINAL LOCATIONS
Sprinkler
Supervisory Signal
Note: Cut TBL jumper on 4XTMF module to
send alarm/trouble signal from the same pair or
terminals.
Fire Alarm Control Panel
(terminal blocks are not shown in their
actual positions in order to clarify wiring
connections)
Alarm/Trouble
Signal
4XTMF Module
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
*Note: For more
information, refer to
Keltron manual.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms mrp-2001eFire-lite alarms mrp-2001c

Table of Contents