The following figure illustrates the connections between the FACP and Keltron Receiver/Transmitter.
P
!
IMPORTANT! All connections between the FACP and Keltron modules must be made within 20 feet and enclosed within conduit or
equivalently protected against mechanical injury.
Keltron 95M3158 TTM-RPS
1.
Terminals 7 and 8: Remote station alarm/trouble inputs.
2.
Terminals 9 and 10: Sprinkler supervisory input.
124

Appendix C: FACP with Keltron

CAUTION: POSSIBLE EQUIPMENT DAMAGE
FOR REASONS OF WIRING DIAGRAM CLARITY, TERMINAL DESIGNATIONS OF KELTRON
MODULES ARE NOT SHOWN IN ACTUAL ORDER. FOLLOW KELTRON MANUAL AND MODULE
MARKINGS FOR EXACT TERMINAL LOCATIONS TO PREVENT SEVERE MODULE DAMAGE!
UL-Listed
Sprinkler Supervisory Signal
(terminal blocks are not shown in their
actual positions in order to clarify wiring
Alarm/Trouble Signal
4XTMF Module
Note: Cut TBL jumper on 4XTMF module to send
alarm/trouble signal from the same pair or terminals.
Fire Alarm Control Panel
connections)
Figure C.1 Keltron Wiring
MS-5UD & MS-10UD Series Manual — P/N 52626:C7 6/12/2018
UL-Listed
*Note: For more
information, refer to the
Keltron manual.