Simplex Contact Closure DACT Installation And Programming Instructions page 42

Digital alarm communication transmitter
Table of Contents

Advertisement

Programming the CCDACT,
Programming (Continued)
Continued
31. Press [↵] or [↓]. Screen displays:
Scroll to select the desired choice. Choices are: 40/60 (40 ms closed, 60 ms
open; used in USA and Canada) and 66/33 (66 ms closed, 33 ms open; used
in Europe).
Note:
Menu items 32 through 48 are automatically set at the default codes
shown in the following example that agrees with the Comm Format
selection chosen for menu item 05. For example, if 4/2 is selected from
menu item 05, Default Code A1 is automatically entered in the selection
field. Entries for 4/2 and 3/1 are user-editable to agree with the report
convention used by the interconnected receiver. The entries for the SIA
and BFSK formats are not editable.
32. Press [↵] or [↓]. Screen displays:
Type in the appropriate report code.
If COMM format is:
Then Item 32 selection must be:
33. Press [↵] or [↓]. Screen displays:
Type in the appropriate report code.
If COMM format is:
Then Item 33 selection must be:
3-12
firealarmresources.com
31>PULSE DIAL RATIO
[40/60 MAKE/BREAK]
32>RC ALARM
[A1 ]
4/2
SIA
BFSK
3/1
A1
FA1
11
1
33>RC PRIORITY2
[A2 ]
4/2
SIA
BFSK
3/1
A2
UA2
22
2
Continued on next page