Programming the CCDACT,
Programming(Continued)
Continued
Prior to selecting the Comm Format Codes, determine the required reporting
format from an authorized person at the central station. Choices are:
•
3/1 pulse = Three-digit account code followed by one-digit
reporting code, double round at 20 pulses per second (PPS).
Programmable reporting codes.
•
4/2 pulse = Four-digit account code followed by two-digit
reporting code, double round at 20 PPS. Programmable reporting
codes. (Default account code.)
•
BFSK = Three-digit account code followed by two-digit reporting
code, single transmission of constant tones. Features built-in error
checking and fixed reporting codes.
•
SIA = Three-digit account code followed by two-digit reporting
code, Level 1 compatibility. Features tonal acknowledge, basic
reports, and fixed reporting codes.
Important: To correctly select the "3/1" format,
a.
Change COMM FORMAT #2 (location 06) to SIA or BFSK.
b.
Change COMM FORMAT #1 (location 05) to 3/1.
c.
Change COMM FORMAT #2 (location 06) to 3/1.