Programming the CCDACT,
Programming (Continued)
Continued
21. Press [↵] or [↓]. Screen displays:
Scroll to the choice that identifies the phone line(s) you want to use to report
this condition.
Note:
Menu items 22 and 23 are automatically default-set as "YES" and are
not user-editable.
22. Press [↵] or [↓]. Screen displays:
23. Press [↵] or [↓]. Screen displays:
24. Press [↵] or [↓]. Screen displays:
Type in the time (in 24 hr format) when the CCDACT is to automatically
report on its operation. Check with the monitoring service provider for the
correct value for this time.
25. Press [↵] or [↓]. Screen displays:
In continental hours, type in the length of a power outage that, when
exceeded, generates an AC FAIL report.
Note:
The CCDACT must not be programmed for delays of 1, 2, 3, 4, or 5
hours. If the host FACP performs the appropriate delay, a value of zero
may be entered here.
3-10
firealarmresources.com
21>ST OFF-NORM@TEST
[P1 ELSE P2]
22>MONITOR LINE 1
[YES]
23>MONITOR LINE 2
[YES]
24>AUTO TST RPT TIME
[02:00]
25>AC FAIL RPT DELAY
[06]
Continued on next page