Installing the 4100/4120-0153 CCDACT Kit,
Wiring the 4100/4120-0153
CCDACT into the System
Note:
Unless otherwise noted, wiring is not supervised.
1.
Wire the 4100/4120-0153 CCDACT into the system in accordance with
Figure 2-8 and the references that follow the figure.
2.
Route the TELCO cables using separate paths from the panel exit to the
RJ-31X modules.
3.
Use the cable tie-wrap (supplied) to provide strain relief for these cables.
Secure the cables to any grounded standoff or metal fixture along the cable
run between the CCDACT and the panel exit.
1
TB1
1
+
Alarm
-
+
Trouble
-
+
Super
2
3
-
+
PRI 2
2
3
-
+
AC Fail
-
+
Comm OK
-
3
P1
TB2
3
1
1
1
4
To Programmer
RS232
2 TxD Out
9 Common
10 RxD In

Figure 2-8. Wiring the 4100/4120-0153 CCDACT into the System

Figure References:
1.
Factory connections:
a.
For a 4100/4120 wall-mount panel, see Table 2 and 841-845 interconnection
diagrams.
b.
For a 4100/4120 rack-mount panel, see Table 2 and 841-869 interconnection
diagrams.
2.
If the supervisory or PRI 2 channels are not used, leave these inputs open.
3.
4100 AUX RELAY cards (8 or 4 point) - Connect CCDACT TB1-12 COMM-OK output
to a feedback point on RELAY card motherboard (FBx+), preferably same relay point as
AC FAIL. Leave TB1-11 unconnected. Connect CCDACT inputs Supervisory/Priority
2/AC Fail to NO and C relay contacts.
4.
Cable connection to programmer is only present during setup.
5.
CCDACT Self-test switch: Slide to "ON" position for self-test. Return to "OFF" position
for normal operation.
6.
Power-limited wiring; route TELCO cable from terminal blocks to left side of panel, and
exit top-left of enclosure. Using harness STR P/N 2080-9046 (7 ft cable), -9047
(14 ft cable), or equivalent, connect to TELCO jacks. Splice as required using 22 AWG
wire (minimum) to complete desired span. TELCO wiring is supervised.
2-13
firealarmresources.com
Continued
Contact Closure DACT
565-627
TB3
TB4
1
1
(BLU)
HOUSE-R1
(RED)
RING 1
5
(GRN)
TIP 1
(GRY)
HOUSE-T1
(BLU)
HOUSE-R2
(RED)
RING 2
(GRN)
TIP 2
(GRY)
HOUSE-T2
Continued on next page