Installing the 4020-0153 CCDACT Kit
Mounting into the 4020 Panel
BRACKET
CCDACT
Note:
If your 4005 panel has firmware that is at Revision 1.01.01, read the
"4005 and 4020/4100/4120 Installations" section (on page 2-3) before
starting the procedure below.
1.
(If applicable) Disconnect one of the two battery terminals; then remove AC
power at the power source.
2.
(If applicable) Disconnect and remove the optional City Card(s). Tie off
and remove the City Circuit wiring.
3.
Using four screws (provided), secure the CCDACT to its bracket (also
provided), then mount the bracket either behind the front panel display or
elsewhere in the panel as shown. (For wiring information, refer to "Wiring
the 4020-0153 CCDACT into the System," which follows this section.)
CCDACT
AND BRACKET
Figure 2-5. Installing a 4020-0153 CCDACT Kit
2-8
firealarmresources.com
REGISTRATION LABEL
Continued on next page