Simplex Contact Closure DACT Installation And Programming Instructions page 37

Digital alarm communication transmitter
Table of Contents

Advertisement

Programming the CCDACT,
Programming (Continued)
Continued
6.
Press [↵] or [↓]. Screen displays:
Scroll to the desired format. (See Page 3-5 for information on Format
Code choices.)
7.
Press [↵] or [↓]. Screen displays:
Type in the number that identifies Phone Line 1's location to the central
station (4 digits maximum with Code 4 / 2).
8.
Press [↵] or [↓]. Screen displays:
Type in the number that identifies Phone Line 2's location to the central
station (4 digits maximum with Code 4 / 2).
9.
Press [↵] or [↓]. Screen displays:
Scroll to the choice that identifies the phone number(s) you want to use to
report this condition. Choices are:
Phone 1 else Phone 2 (default)
Both Phone 1 and Phone 2
Phone 1 only
Phone 2 only
None (valid only for unused inputs)
Note:
The above choices also apply to menu items 10 through 21.
3-7
firealarmresources.com
06>COMM FORMAT #2
[4/2]
07>ACCOUNT #1
[
]
08>ACCOUNT #2
[
]
09>ST ALARM
[P1 ELSE P2]