Interconnection Table - Simplex Contact Closure DACT Installation And Programming Instructions

Digital alarm communication transmitter
Table of Contents

Advertisement

Installing the 4020-0153 CCDACT Kit,

Interconnection Table

Continued
Use Table 2-1 along with the 841-906 interconnection diagram when wiring the
4020-0153 CCDACT into your system. (See Figure Reference 1 on page 2-10.)
Table 2-1. CCDACT / 4020 Wiring
CCDACT
WIRE COLOR
TB1-1
ORANGE
TB1-2
RED
TB1-3
BLUE
TB1-4
BLACK
TB2-1
RED
TB2-2
BLACK
2-11
firealarmresources.com
4020
CPU CARD [TB1 - CITY (NO)]
CPU CARD [TB1 - CITY (+)]
CPU CARD [TB1 - TBL (NO)]
CPU CARD [TB1 - TBL (C)]
POWER INTERFACE (I/F) CARD
[TB3 (+24V)]
POWER I/F CARD [TB3 (0V)]